Danfoss CTI 100 Circuit breakers with built-in current limiter

The Danfoss CTI product range is modular, flexible and offers a large selection of clip-on auxiliary functions and accessories: Aux. contacts, alarm contacts, voltage- and under-voltage trips.

 

 

 

 

• Compact design
• DIN rail mounting
• Motor application
• Short-circuit protection
• Overload protection of motors (31.5 - 45 kW)
• Setting range: 40 - 90A
• Operation switch (manual motor starter)
• Isolation switch (with locking device)
• Emergency switch (with undervoltage trip)
• Indications:
• Test and reset functions
• ON or OFF
• Thermal and electromagnetic trip

Features
• Overload protection and short circuit protection of motor installations.
• Test function for thermal trip
• Manual reset function
• Indication for thermal trip
• Indication for magnetic trip (short circuiting)
• Single phase protection (Differential trip)
• Temperature compensated (-20 0C to + 60 0C)
• Tripping class 10

Approvals
GL-Germanischer Lloyd  Current limiter, CTL 65
GL-Germanischer Lloyd  Circuit breaker, CTI 25
UL-Underwriters Laboratories inc.  Circuit breaker, CTI 16T;CTI 20TB;CTI 25M;CTI 25MB;CTI 25S;CTI 25SB;CTI 32TB;CTI 45MB;CTI 45SB

 

Code number

Type

Current range [A]

Max. load, AC-3 [kW]

Max. trip current [A]

Breaking cap. Ics 380 - 415 V

047B3002

CTI 100

63,00 - 90,00 A

45,00 kW

1.260,0 A

25 kA

047B3014

CTI 100

40,00 - 63,00 A

31,50 kW

882,0 A

50 kA

047B3015

CTI 100

63,00 - 90,00 A

45,00 kW

1.260,0 A

25 kA

 

Click to buy Danfoss CTI 100 online
Click to view Danfoss CTI 100 technical